Compact and performance-packed, this power controller provides an economical and versatile solid state option for controlling electric heat. In addition, it is 200KA SCCR with proper fusing to minimize damage in the event of a short circuit and features a 24 to 48 V AC line/load voltage and a 4 to 20 mA DC control input.
Compact and performance-packed, this power controller provides an economical and versatile solid state option for controlling electric heat. In addition, it is 200KA SCCR with proper fusing to minimize damage in the event of a short circuit and features a 24 to 48 V AC line/load voltage and a 4 to 20 mA DC control input.
Features
Applications
Operator Interface | Control input Input indication LED |
Amperage | Single-phase, see the output rating curve Maximum I2t for fusing: 4000 A2 sec Latching current: 400 mA maximum Holding current: 200 mA maximum Power dissipation is 1.2 W/A switched 200KA SCCR, Type 1 and 2 approved with the recommended fusing |
Line Voltage | 24 to 48 V AC Off-state leakage: 1 mA at 77°F (25°C) maximum 50/60 Hz independent |
Control Mode, Zero Cross | 4 to 20 mA DC input, variable time-base control output (3 cycles on, 3 cycles off at 50% power) |
Control Input | Loop powered linear current 4 to 20 mA DC: loop-powered, control option F0 only (requires current source with 8.0 V DC available, no more than two DIN-A-MITE inputs can be connected in series) |
Terminals | Control input: Compression: Will accept 24 to 16 AWG (0.2 to 1.5 mm2) wire Line and load: Compression: Will accept 18 to 8 AWG (0.8 to 8.4 mm2) wire |
Operating Environment | -4 to 176°F (-20 to 80°C); see the output rating curve chart for your application 0 to 90% RH (relative humidity), non-condensing Insulation tested to 9842.52' (3000 m) Suitable for "Pollution degree 2" |
Agency Approvals | CE with proper filter: 204/108/EC Electromagnetic Compatibility Directive EN 61326-1: Industrial Immunity Class A Emissions 2006/95/EC Low Voltage Directive EN 50178 Safety Requirements Installation category III, pollution degree 2 UL® 508 listed and C-UL® File E73741 2011/65/EU RoHS 2 |
Mounting | Options include DIN-rail or standard back panel mounting DIN EN 50022, 1.4 x 0.3" (35 x 7.5 mm) Mount cooling fins vertically |
Dimensions | 3.7 x 2 x 3.9" (94 x 50 x 98 mm) |
Weight | 0.71 lbs (0.32 kg) |
Operator Interface | Control input Input indication LED |
Amperage | Single-phase, see the output rating curve Maximum I2t for fusing: 4000 A2 sec Latching current: 400 mA maximum Holding current: 200 mA maximum Power dissipation is 1.2 W/A switched 200KA SCCR, Type 1 and 2 approved with the recommended fusing |
Line Voltage | 24 to 48 V AC Off-state leakage: 1 mA at 77°F (25°C) maximum 50/60 Hz independent |
Control Mode, Zero Cross | 4 to 20 mA DC input, variable time-base control output (3 cycles on, 3 cycles off at 50% power) |
Control Input | Loop powered linear current 4 to 20 mA DC: loop-powered, control option F0 only (requires current source with 8.0 V DC available, no more than two DIN-A-MITE inputs can be connected in series) |
Terminals | Control input: Compression: Will accept 24 to 16 AWG (0.2 to 1.5 mm2) wire Line and load: Compression: Will accept 18 to 8 AWG (0.8 to 8.4 mm2) wire |
Operating Environment | -4 to 176°F (-20 to 80°C); see the output rating curve chart for your application 0 to 90% RH (relative humidity), non-condensing Insulation tested to 9842.52' (3000 m) Suitable for "Pollution degree 2" |
Agency Approvals | CE with proper filter: 204/108/EC Electromagnetic Compatibility Directive EN 61326-1: Industrial Immunity Class A Emissions 2006/95/EC Low Voltage Directive EN 50178 Safety Requirements Installation category III, pollution degree 2 UL® 508 listed and C-UL® File E73741 2011/65/EU RoHS 2 |
Mounting | Options include DIN-rail or standard back panel mounting DIN EN 50022, 1.4 x 0.3" (35 x 7.5 mm) Mount cooling fins vertically |
Dimensions | 3.7 x 2 x 3.9" (94 x 50 x 98 mm) |
Weight | 0.71 lbs (0.32 kg) |