Featuring a 40' ETFE cable with a 10 psi range, this tranmitter is designed with a flush diaphragm tip that will not clog in harsh applications such as sewage lift stations. Narrow body design allows the FBLT to fit into stilling wells and narrow installations.
Featuring a 40' ETFE cable with a 10 psi range, this tranmitter is designed with a flush diaphragm tip that will not clog in harsh applications such as sewage lift stations. Narrow body design allows the FBLT to fit into stilling wells and narrow installations.
The unit measures the height of liquid above the position that it is mounted in a tank or pit in reference to atmospheric pressure. Ventilation tube in the cable automatically compensates for changes in atmospheric pressure above the fluid. The vent is protected with a maintenance free filter, eliminating particulate or water droplets from entering the transmitter.
Features
Applications
Service | Compatible liquids |
Wetted Materials | Body: 316 SS; Cable: Polyether polyurethane or ETFE; Diaphragm: PTFE coated FKM fluoroelastomer; Label: Polyethylene polyamid |
Accuracy | ±0.25% FS (10' w.c. range is ±0.30% FS) |
Temperature Limits | -4 to 176°F (-20 to 80°C) |
Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
Thermal Effect | ±0.0075%/°F (±0.0135%/°C) |
Pressure Limit | 2x range |
Power Requirements | 10 to 33 VDC |
Output Signal | 4 to 20 mA DC 2-wire |
Response Time | < 50 ms |
Max Loop Resistance | 1000 Ω @ 30 VDC |
Electrical Connections | Wire pigtail |
Mounting Connection | Suspended below point being monitored |
Electrical Protection | Surge/lightning protected per EN61000-4-5, Class 5 |
Weight | Body: 0.3 lb (0.136 kg); Cable: 0.037 lb (0.017 kg) per foot |
Agency Approvals | CE |
Service | Compatible liquids |
Wetted Materials | Body: 316 SS; Cable: Polyether polyurethane or ETFE; Diaphragm: PTFE coated FKM fluoroelastomer; Label: Polyethylene polyamid |
Accuracy | ±0.25% FS (10' w.c. range is ±0.30% FS) |
Temperature Limits | -4 to 176°F (-20 to 80°C) |
Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
Thermal Effect | ±0.0075%/°F (±0.0135%/°C) |
Pressure Limit | 2x range |
Power Requirements | 10 to 33 VDC |
Output Signal | 4 to 20 mA DC 2-wire |
Response Time | < 50 ms |
Max Loop Resistance | 1000 Ω @ 30 VDC |
Electrical Connections | Wire pigtail |
Mounting Connection | Suspended below point being monitored |
Electrical Protection | Surge/lightning protected per EN61000-4-5, Class 5 |
Weight | Body: 0.3 lb (0.136 kg); Cable: 0.037 lb (0.017 kg) per foot |
Agency Approvals | CE |